230V Intelligent ATS banner

Overview

The leading edge ATS solution provides the widest range of configurations with shortest lead-times in the market : It offers models with input range from 10A to 32A, outlet number from 1 to 24 and variety of outlet types ( e.g. C13, C19, C13+C19, UK, Schuko, French, IEC309, etc ). Custom configurations are available upon request.

Model & Drawing

Dual Circuit - 2U Outlets Amp Inlet
3M cord attached
C13 C19 IEC309
[pdf] ATS-H16C13-32A-W_EN 16 32A EN60309
[pdf] ATS-H20C13-32A-W_EN 20 32A EN60309
[pdf] ATS-H24C13-32A-W_EN 24 32A EN60309
[pdf] ATS-H16C13 / 2C19-32A-W_EN 16 2 32A EN60309
[pdf] ATS-H16C13 / 4C19-32A-W_EN 16 4 32A EN60309
[pdf] ATS-H8C19-32A-W_EN 8 32A EN60309
[pdf] ATS-H10C19-32A-W_EN 10 32A EN60309
[pdf] ATS-H12C19-32A-W_EN 12 32A EN60309
[pdf] ATS-H2EN16A-32A-W_EN 2 32A EN60309
[pdf] ATS-H1EN32A-32A-W_EN 1 32A EN60309
Customization available on request

Specification

Electrical
Nominal input voltage 200 ~ 230V
Acceptable input voltage ±10% nominal
Input frequency 50 / 60 Hz
Inlet plug & cord 2 x C14 / C20 / EN 60309 / BS1363 / CEE7 plug with 3M cord
Outlet connectors C13 / C13+C19 / C19 / IEC309 / UK / Schuko / FR
Local meter Field replaceable 1.8" color LCD
Overload protection 1 x 10-amp circuit breaker for C14 inlet
1 x 13-amp circuit breaker for BS1363 inlet
1 x 16-amp circuit breaker for C20 / EN16 60309 / CEE7 inlet
1 x 20-amp circuit breaker for Open-end
2 x 16-amp circuit breaker for EN32 60309 inlet
Transfer time 10 - 16ms typical
Electrical endurance 1 x 106 operations
Physical
1U Product ( W x D x H ) 442 x 270 x 43.5 mm
Packing ( W x D x H ) 540 x 540 x 150 mm
Net weight 4.7 kg / 10.3 lb
Gross weight 5.2 kg / 11.4 lb
2U Product ( W x D x H ) 442 x 270 x 87.5 mm
Packing ( W x D x H ) 540 x 540 x 150 mm
Net weight 6.6 kg / 14.5 lb
Gross weight 7.1 kg / 15.6 lb
Chassis color Dark
Chassis materials Steel
Environmental
Operating temperature -5 to 60°C ( 23 to 140°F )
Storage temperature -25 to 65°C ( 13 to 149°F )
Operating humidity 0~95%, non-condensing
Storage humidity 0~95%, non-condensing
Compliance
EMC FCC & CE certified
Safety LVD certified
Environment RoHS2 & REACH compliant